Installation type/mounting | ||||
Mounting | on 35 mm DIN rail, 2 spacing units wide | |||
Supply voltage | ||||
Rated value (DC) | ||||
● 24 V DC | Yes | |||
permissible range, lower limit (DC) | 20.4 V | |||
permissible range, upper limit (DC) | 28.8 V | |||
Rated value (AC) | ||||
● 24 V AC | Yes | |||
Line frequency | ||||
● permissible range, lower limit | 47 Hz | |||
● permissible range, upper limit | 63 Hz | |||
Digital inputs | ||||
Number of digital inputs | 4 | |||
Input voltage | ||||
● Type of input voltage | AC/DC | |||
● for signal "0" | < 5 V AC/DC | |||
● for signal "1" | > 12 V AC/DC | |||
Input current | ||||
● for signal "0", max. (permissible quiescent current) | 1.1 mA | |||
● for signal "1", typ. | 2.63 mA | |||
Input delay (for rated value of input voltage) | ||||
for standard inputs | ||||
— at "0" to "1", max. | 1.5 ms | |||
— at "1" to "0", max. | 15 ms | |||
Digital outputs | ||||
Number of digital outputs | 4; Relays | |||
Short-circuit protection | No | |||
Controlling a digital input | Yes | |||
Switching capacity of the outputs | ||||
● on lamp load, max. | 1 000 W | |||
Output current | ||||
● for signal "1" rated value | 5 A | |||
● for signal "1" minimum load current | 100 mA | |||
Parallel switching of two outputs | ||||
● for uprating | No | |||
Switching frequency | ||||
● with resistive load, max. | 2 Hz | |||
● with inductive load, max. | 0.5 Hz | |||
● mechanical, max. | 10 Hz | |||
Relay outputs | ||||
Switching capacity of contacts | ||||
— with inductive load, max. | 3 A | |||
— with resistive load, max. | 5 A | |||
EMC | ||||
Emission of radio interference acc. to EN 55 011 | ||||
● Limit class B, for use in residential areas | Yes | |||
Degree and class of protection | ||||
IP degree of protection | IP20 | |||
Standards, approvals, certificates | ||||
CE mark | Yes | |||
CSA approval | Yes | |||
UL approval | Yes | |||
FM approval | Yes | |||
developed in accordance with IEC 61131 | Yes | |||
certificate of suitability / according to VDE 0631 | Yes | |||
Marine approval | Yes | |||
Ambient conditions | ||||
Ambient temperature during operation | ||||
● min. | 0 °C; ES03 and higher: -20 °C | |||
● max. | 55 °C | |||
Dimensions | ||||
Width | 35.5 mm | |||
Height | 90 mm | |||
Depth | 58 mm |